Following our business strategy to meet the needs of our customers, we seek to optimize resources technically and financially, guaranteeing delivery times and thus ensuring the quality of our facilities with maximum environmental safety.

Sectors of action

Engineering

  • Design of critical areas, clean or contracted decontamination.
  • Construction of infrastructure, including civil works.
  • Air conditioning systems, air filtration and energy saving.
  • Fluids for processes: production of treated water, management and inactivation of biocontaminants.
  • Auxiliary facilities such as steam, compressed air, gases, vacuum.
  • Integrated equipment such as laminar flows, decontamination locks, air showers.
  • Supply and assembly of equipment for production and research.
  • Pollutant simulations.
  • Qualification of the facilities.
  • Process validation.
  • Computer validation.

Infrastructure

  • Enclosures specially designed for clean areas or biocontainment areas.
  • Based on a modular construction system, self-supporting, easy to clean and decontaminate, inorganic, impermeable to liquids and resistant to chemical agents that can be used for cleaning and decontamination.
  • Sandwich panels for the execution of the walls, finished in phenolic resins, lacquered steel sheet or stainless steel and with polystyrene core, aluminum honeycomb or rock wool.
  • The windows perfectly flush on both sides of the panel.
  • The doors and profiles for auctions have been designed with curved shapes to avoid the accumulation of dust and its easy cleaning.
  • Watertight doors with inflatable seal strip for BSL-3 biocontainment areas.
  • The modular or continuous roofs allow to be visited for a comfortable maintenance of the facilities.

Class 10,000 clean room installation - University of Valencia - Corpuscular Physics Institute

  • Room type: 10,000 according to USA standard FED-STD 209 D.
  • Useful room sizes: general space class 10,000: 70.31 m2.
  • Number of people working: 11 people.
  • Useful working area per person: 7.29 m2.
  • Free height of room: 2.50 m.
  • Process equipment: existing.
  • Output flow / hour: 2 people.
  • Safety clothing: complete.
  • Thermal currents: no
  • Internal pressurization: 250 Pa.
  • Movements air / hour: between 30 and 70 renewals / h.
  • Entry-exit lock: mandatory and class 100,000.
  • Drive surface in ceiling: 7.75%.
  • Air return: lower room area.
  • Quality and type of filters:
    • 1st stage: pre-filters EU-3 - Efficiency 35%.
    • 2nd stage: bag filters type EU-8/9 - Efficiency 95%.
    • 3rd stage: absolute filters type EU-13/14 - Efficiency: 99.997%.
  • Type of air flow: multidirectional.

Class 1,000 clean room installation - University of Valencia - Gace - Astronomy and Space Sciences Group

  • Class of room: 1000 according to USA FED-STD 209 D standard.
  • Useful room sizes: general space class 1000: 38.29 m2.
  • Number of people working: 4 people.
  • Useful working area per person: 9.57 m2.
  • Free height of room: 2.85 m.
  • Process equipment: existing.
  • Output flow / hour: 2 people.
  • Safety clothing: complete.
  • Thermal currents: no.
  • Internal pressurization: 250 Pa.
  • Movements air / hour: between 70 and 300 renewals / h.
  • Entry-exit lock: mandatory and class 1000.
  • Drive surface in ceiling: 20% - 50%.
  • Air return: lower room area.
  • Quality and type of filters:
    • 1st stage: pre-filters EU-3 - Efficiency 35%.
    • 2nd stage: bag filters type EU-8/9 - Efficiency 95%.
    • 3rd stage: absolute filters type EU-13/14 - Efficiency 99.997%.
  • Type of air flow: multidirectional.

Class 10,000 clean room installation - Cyclotron room - Alboraya industrial estate (Valencia)

  • Class of room: 1000 according to USA FED-STD 209 D standard.
  • Useful room sizes: general space CLASS 1000: 20.88 m2.
  • Number of people working: 2 people.
  • Useful working area per person: 10.44 m2.
  • Free height of room: 2.60 m.
  • Process equipment: existing.
  • Output flow / hour: 2 people.
  • Safety clothing: complete.
  • Thermal currents: no.
  • Internal pressurization: 250 Pa.
  • Movements air / hour: between 30 and 70 renewals / h.
  • Entry-exit lock: mandatory and class 100,000.
  • Drive surface in ceiling: 6.56%.
  • Air return: lower room area.
  • Quality and type of filters:
    • 1st stage: pre-filters EU-3 - Efficiency 35%.
    • 2nd stage: bag filters type EU-8/9 - Efficiency 95%.
    • 3rd stage: absolute filters type EU-13/14 - Efficiency 99.997%.
  • Type of air flow: multidirectional.

Clean room installation class 10000 - University of Valencia - ICMOL - Institute of Molecular Science

  • Class of room: 10000 according to USA standard FED-STD 209 D.
  • Useful room sizes: general space class 10000: 46.25 m2.
  • Number of people working: 3 people.
  • Useful working area per person: 13.64 m2.
  • Free height of room: 2.50 m.
  • Process equipment: existing.
  • Output flow / hour: 2 people.
  • Safety clothing: complete.
  • Thermal currents: no.
  • Internal pressurization: 25 Pa.
  • Movements air / hour: between 30 and 70 renewals / h.
  • Entry-exit lock: mandatory.
  • Drive surface in ceiling: 3.89%.
  • Air return: lower room area.
  • Quality and type of filters
    • 1st stage: pre-filters EU-3 - Efficiency 35%.
    • 2nd stage: bag filters type EU-8/9 - Efficiency 95%.
    • 3rd stage: absolute filters type EU-13/14 - Efficiency 99.997%.
  • Type of air flow: multidirectional.

109/5000 Clean room class 10,000 - University Hospital La Fe - Research Center and Cell Therapy Unit

  • Class of room: 10000 according to USA standard FED-STD 209 D.
  • Useful room sizes: CLASS 10000 general space: 52.00 m2.
  • Number of people working: 4 people.
  • Useful working area per person: 7.43 m2.
  • Free height of room: 2.50 m.
  • Process equipment: existing.
  • Output flow / hour: 1 person.
  • Safety clothing: complete.
  • Thermal currents: no.
  • Internal pressurization:> 10 Pa.
  • Movements air / hour: between 30 and 70 renewals / h.
  • Entry-exit lock: mandatory.
  • Drive surface in ceiling: 20% - 50%.
  • Air return: lower room area.
  • Quality and types of filters:
    • 1st stage: EU-4 (G4).
    • 2nd stage: EU-7 (F7).
    • 3rd stage: absolute filters type EU-14-efficiency: 99.997%.
  • Type of air flow: multidirectional.